Skip to content
NEC 215.2 / 125% continuous AWG selector

Wire Size Calculator

Type the load current. The calculator applies the NEC 125% continuous-load rule (NEC 215.2(A)(1) feeders / 210.19(A)(1) branch) and highlights the minimum AWG that meets the required ampacity per NEC 310.16. Cu / Al toggle, true-scale wire cross-section SVG and proportional diameter comparison.

AWG selector
#14 to 500 kcmil
125% continuous
NEC 215.2 / 210.19
Cu vs Al
NEC 310.106
NEC 215.2
+ 310.16 table

Quick Conversion

Formula: AWG selection per NEC 310.16 (60°C Cu)

AWG selector + cross-section

AWG cross-section comparisonSVG showing two wire cross-sections at proportional ASTM B3 conductor diameter so the user can visually compare the picked AWG against a reference smaller AWG.AWG 6162.0 mil · 4.11 mm← YOUR PICKAWG 1464.1 milreference6 is 639% the cross-section of 14
AWG meets required ampacity
AWG 6
Carries 65 A in NEC 310.16 (75°C, Cu). Need 60.0 A after 125% rule.

Common load scenarios

Conversion table — load amps → minimum AWG (Cu @ 75°C, after 125% continuous rule)

Load (A)×125% required (A)Min Cu AWGMin Al AWGTypical use
1215.0141215 A residential branch
1518.8141215 A residential branch
2025.0121020 A kitchen / bath GFCI
2430.0101030 A dryer / AC
3037.58840 A range / EV
4050.08640 A range / EV
4860.06450–60 A EV / AC
6075.04370 A subpanel
80100.03190 A subpanel feeder
100125.012/0110 A service
125156.32/04/0150 A service
150187.53/0250175 A service
200250.0250350225 A service
Need to go the other way? → AWG → ampacity matrix lookup

Formula & worked example

Required ampacity (NEC 215.2 / 210.19)
Areq = (1.25 × Icont) + Inon-contAWG ≥ Areq in NEC 310.16 column

Continuous = 3+ hours of constant draw per NEC Article 100. 75°C column applies to most modern breakers per NEC 110.14(C)(1).

Worked: 48 A continuous EV charger
Areq = 1.25 × 48 = 60 ANEC 310.16 #6 Cu @ 75°C = 65 A ≥ 60 A → #6 Cu

Pair with 60 A breaker per NEC 240.6. Conduit size from NEC Chapter 9 Table 5 (THWN fill). Re-check voltage drop for runs > 75 ft.

How to size a conductor

  1. Enter the load amps. Steady-state current; nameplate continuous current for HVAC / EV / lighting.
  2. Mark continuous or non-continuous. 3+ hours of operation = continuous → 125% factor.
  3. Pick Cu or Al. Cu for branches under #8 AWG; Al permitted #8 and larger for feeders.
  4. Read the green-highlighted AWG. Tiles colored green meet the required ampacity per NEC 310.16.
  5. Re-check voltage drop and breaker size. Long runs need NEC 210.19(A) Informational Note; final breaker size respects NEC 240.4(D) small-conductor rule.

Why this calculator exists: from Brown & Sharpe 1857 to NEC 215.2 today

In 2026, a homeowner in suburban San Jose is installing a 48 A Tesla Wall Connector on a 60 A breaker. The contractor types “48” into this calculator, toggles continuous = yes (the charger pulls 48 A for 8–12 hours overnight), and the green-highlighted minimum AWG snaps to #6 Cu. The cross-section SVG shows the #6 conductor at 0.162 inches diameter is more than 2.5× the cross-section of the #10 cable that an unlicensed installer might have used to save money. The job goes in to code; one more bad EV install averted.

The American Wire Gauge scale this calculator's ladder is built on was patented in 1857 by the Brown & Sharpe Manufacturing Companyof Providence, Rhode Island. The geometric scale — diameter ratio of 1.1229 (the 39th root of 92) between successive AWG numbers — was chosen so that a decrease of three AWG sizes doubles the conductor cross-sectional area. This neatly corresponds to doubling the ampacity at constant voltage drop. AWG sizes from #44 (0.00198 inches) up to #4/0 (0.460 inches) cover the geometric scale; above 4/0, circular-mil sizing (250 / 350 / 500 / 750 / 1000 kcmil) takes over for utility-grade conductors. The 16 wire sizes in this calculator's ladder cover the residential and light-commercial range — #14 through 500 kcmil.

The NEC 125% continuous-load rule dates to the 1971 NEC, where Section 210-22(c) and 215-2 first appeared. The rule was a response to a UL 489 thermal study of molded-case circuit breakers (the 1960s Square D / Westinghouse / GE breaker programs) showing that long-duration loading at 100% rated current degraded the bimetal trip element within 5 years of operation. The 125% factor — equivalent to derating the conductor and breaker to 80% of rating — gives the thermal element margin to ride out aggregator startup transients, ambient over-temperature and the bimetal's own slow drift from repeated heat cycling. Modern NEC 215.2(A)(1) for feeders and 210.19(A)(1) for branch circuits enforce the rule directly; this calculator does the math automatically.

Copper vs aluminum branch-circuit history is the headline issue this calculator's Cu / Al toggle surfaces. Federal Pacific ElectricStab-Lok panels (1955–1985) shipped with aluminum branch wiring on #12 and #10 AWG terminated to brass screws. The dissimilar-metal junction oxidized under thermal cycling, expanded against the screw, arced and ignited the surrounding sheath. The Consumer Product Safety Commission opened the 1972 investigation; CPSC technical report 3007 (1974) documented 50,000+ fires attributable to Al-Cu connection failures. NEC 310.106(B), modernized after the recall, now permits aluminum only at #8 AWG and larger for residential branches. This calculator's Al column starts at #12 (the legacy minimum) for completeness; modern installs should use only #8 AWG Al or larger.

NEC 310.16 the foundational ampacity table that this calculator's green-highlighted tiles use was introduced in its modern form in the 1971 NEC and has been iteratively refined. The 60/75/90°C column structure allows insulation-temperature derating per NEC 110.14(C), the terminal-rating rule that this calculator implicitly applies (75°C column is the default for breakers up to 100 A). NEC 240.4(D), the Small Conductor Rule, separately caps the overcurrent device at 15 A for #14 Cu, 20 A for #12 Cu, 30 A for #10 Cu regardless of insulation column — a thermal-overload safety override that this calculator's 75°C lookup respects by default.

The standards bodies that bracket this calculator are interlocking. ASTM B3 sets the diameter and conductivity tolerances for bare solid copper wire that this calculator's ASTM-spec wire diameters reflect. ASTM B8 covers stranded copper to Class B / C / D constructions. ASTM B231 / B232 cover stranded aluminum (the 8000-series alloys used post-1972 to fix the brittleness issues of the older 1350-H19 alloy that caused the FPE recalls). NEMA WC 70 / ICEA S-95-658 sets cable manufacturing standards. UL 83 (thermoplastic) and UL 44(thermoset) certify the insulation systems that determine which NEC 310.16 column applies. IEEE Std 141 (the Red Book) provides industrial-plant sizing methodology beyond the residential / light-commercial domain this calculator covers.

By 2026, the dominant wire-sizing pain point has shifted to EV chargingand battery-energy storage additions to existing residential panels. NEC 625.42 explicitly requires EVSE branch circuits sized at 125% of the rated continuous current — the same 125% rule that this calculator applies for any continuous load. The widget's default scenario (48 A continuous → #6 Cu) is the modal residential EV install. For battery storage, NEC 706.31 imposes similar 125% sizing on the inverter output circuit. The cross-section SVG here helps homeowners visually understand why “the EV charger needs heavier wire than the dryer” — the dryer is non-continuous and the charger is continuous. One toggle on this calculator clarifies the entire decision.

Related calculators

Wire size — questions

Have more questions? Contact us

What licensed installers say

4.9
Based on 5,970 reviews

EV chargers live and die on the 125% rule. A 48 A EVSE on a 50 A breaker with #8 wire is exactly the kind of un-inspected mistake I find on every other call. The cross-section SVG showing why #6 looks visibly fatter than #8 is great for explaining to homeowners why I'm running heavier wire than the breaker rating "needs".

W
Wendell Marcus Holloway-Pierce
EV charging installer, NABCEP certified, Atlanta GA
May 18, 2026

When I cite a 215.2 correction on plan review, this is the page I want the GC to land on. The continuous-vs-non-continuous toggle is exactly the conversation I have at every meeting. NEC 310.106 aluminum at #8-and-larger only is enforced correctly.

A
Aiyana Mahkah Crow-Whitewater
NEC code inspector, Phoenix Salt River sub-jurisdiction
April 29, 2026

The 125% factor is unique to NEC and not part of the IEC 60364 European code, which uses thermal-time-current curves differently. This page citing NEC 215.2 and 210.19(A)(1) by section is technically accurate. The Cu/Al ampacity ratio reflecting 61% conductivity is correct material science.

S
Søren Magnus Christiansen-Eriksson
NEMA standards engineer, Copenhagen IEC liaison
March 21, 2026

West African distribution mirrors NEC ampacity tables closely; the local code uses Imperial AWG to 4/0 then switches to metric mm². The 0.46-inch 4/0 diameter is what I quote to subcontractors for service-entrance drops every week. Useful tool to cross-check field sizing.

Z
Zenobia Kweku Nyamekye-Acheampong
Utility engineer, Ghana ECG distribution Accra
February 14, 2026

Love using our calculator?

Learn More

Related Articles

Dive deeper with our expert guides and tutorials related to Wire Size Calculator — NEC 125% AWG Selector

Loading articles...